Permit Number: T15CM00076
Parcel: 113111950

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T15CM00076
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/12/2016 STEVE SHIELDS ZONING REVIEW Reqs Change P&DS TRANSMITTAL


FROM: Steve Shields,
Principle Planner

PROJECT:
T15CM00076
1624 E. Waverly Street
Convert existing utility building to sleeping quarters

TRANSMITTAL: August 12, 2016

COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

This site is located in the NR-1 zone (UDC 4.7.8). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A).
Based on a wall height of less than 9'-0" the required perimeter yard setback to the ease property line is 6'-0', proposed perimeter yard setback is 4'-0".
Based on a wall height of less than 10'-2" the required perimeter yard setback to the ease property line is 6'-9', proposed perimeter yard setback is 6'-0".

Neighborhood Preservation Zone (NPZ) review is required prior to approval of the plan.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/16/2016 LBOJORQ1 OUT TO CUSTOMER Completed