Permit Review Detail
Review Status: Completed
Review Details: POOL - COMM MODEL
Permit Number - T15BU01496
Review Name: POOL - COMM MODEL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/05/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 01/05/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved |