Permit Number: T15BU01357
Parcel: 11202005A

Review Status: Completed

Review Details: POOL - SPA

Permit Number - T15BU01357
Review Name: POOL - SPA
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/23/2015 PAUL BAUGHMAN ENGINEERING REVIEW Approved
11/23/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Show that adequate clearances exist between the exit of the flue products from the spa heater and any building openings and that roof water drainage will not affect the spa heater. Reference: Section 303.1, IFGC 2012.
11/23/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/23/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Revise the pipe sizes so that the flow rates will not result in water velocities greater than that recommended by the pipe manufacturer (e.g. limit the water velocity to less than 8 FPS for PVC piping). Reference: Table 303.2, IPC 2012.
2. Provide a complete design for the natural gas distribution system for all of the specified gas-fired appliances (pool heaters, BBQ's, and fire pits). Show the all of the loads, developed lengths, and the layout of the distribution piping. Reference: Section 107.2.1, IBC 2012.
11/23/2015 STEVE SHIELDS ZONING REVIEW Approved
11/23/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Passed 1. Provide complete electrical plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
Include all the information as required per, City of Tucson Commercial Electrical Plan Submittal Requirements.