Permit Number: T15BU01172
Parcel: 122010810

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T15BU01172
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/14/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/06/2015 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments on the authorized electrical repair submittal for COT ID# 370 at 4045 East Speedway Boulevard (T15BU01172).


Sheet 1 of 2


No comments.


Sheet 2 of 2


1. Provide police report referenced In 2nd paragraphs of Scope of Work.


2. In 7th paragraph of Scope of Work, provide date and any associated documentation related to TEP disconnecting electrical power at property owner’s request.


3. In Existing Electrical, delete reference to existing D222NRB disconnect or otherwise explain how it is located within or outside of existing main panel.


4. In New Electrical, specify distance between ground rods per NEC minimum.


5. In Partial Site Plan, correct reference to Oracle Rd and associated distance (as applicable to the latter).


6. In Title Block, correct number of sign faces.


7. Revise plans as necessary to reflect repair of damage to incoming and outgoing conduit and wiring at 206 panel.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/12/2016 KROBLES1 OUT TO CUSTOMER Completed