Permit Number: T15BU01030
Parcel: 13216012M

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T15BU01030
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/16/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/22/2015 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments on the authorized repair submittal for COT ID# 280 at 4402 South Kino Parkway (T15BU01030).


Sheet 1 of 3


No comments.


Sheet 2 of 3


1. In North Face Elevation, correct overall billboard height (42’0” shown exceeds actual height by approximately 5’9”).


2. In 3rd & 6th paragraphs of Scope of Work and Apron & Stringer Mounting Detail, correct apron height as applicable (standard apron height for this configuration is 36” rather than 24” shown & existing aprons appear to be 36”).


Sheet 3 of 3


No comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/13/2015 AROMERO4 OUT TO CUSTOMER Completed