Review Details: BILLBOARD - BLDG30days
Permit Number - T15BU01007
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/28/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/27/2015 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Denied | BRC Comments Below are comments on the authorized electrical repair resubmittal for COT ID# 259 at 2001 East Valencia Road (T15BU01007). Resubmittal adds note that remounting of electrical service components directly on I-beam instead of angle iron bracketing is acceptable and not deemed to be a relocation of electrical service. Still request that note be added to permit in this regard or in some other appropriate form to constitute City disclaimer. Sheet 1 of 2 No comments. Sheet 2 of 2 1. In Description of Existing Ballast, revise description of existing lamps from high output to very high output (engineer’s response letter on Comment #8 indicates that this revision was made, but it is not reflected on the plan sheet; handwritten administrative correction without additional review cycle is acceptable). Sheet 3 of 3 No comments. |