Permit Number: T15BU01006
Parcel: 140280290

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T15BU01006
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/09/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/02/2015 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments on the authorized repair submittal for COT ID# 259 at 2001 E. Valencia Rd. (T15BU01006).


Sheet 1 of 2


No comments.


Sheet 2 of 2


1. In 1st & 2nd paragraphs of Scope of Work, revise to reflect replacement of Z-clips...


2. In 1st paragraph of 1st boxed note below Scope of Work, add “(F)” to reflect Z-clip replacement (and delete orphan comma).


3. In Stinger Between Uprights, add note clarifying that there are no fasteners attaching the Z-clips to the metal stringers (or otherwise provide standard details showing any such fasteners)..


4. In East Sign Face Elevation, correct height indicated from base grade to top of face panel (overstated by approximately 2’3”).

Final Status

Task End Date Reviewer's Name Type of Review Description
10/22/2015 KROBLES1 OUT TO CUSTOMER Completed