Review Date Reviewer's Name Type of Review Description Status Comments
08/25/2015 KEN BROUILLETTE FIRE REVIEW Approved
09/08/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change The current submittal did not provide adequate information in order to verify compliance with the National Electrical Code.
Please provide a complete Electrical Site Plan, and any other construction documents as necessary for a complete electrical plan review as required per " City of Tucson Plan Review Submittal Requirements". Plans to be prepared by an Electrical Engineer Registered in the state of Arizona as required per;
R4-30-302. Electrical engineering
A. A registrant shall prepare and submit drawings and specifications for a new electrical system or an addition or modification to an existing electrical system provided the service and associated electrical feeders exceeds 600 amperes 120/240 volts, single phase or 225 amperes 120/208 volts, three phase and the fault current exceeds 10,000 amperes
B. In all cases a registrant shall design:
1. Electrical installations in hospitals or other buildings with surgical operating rooms regulated by Article 517 of the National Electrical code (1990 edition) incorporated herein by reference and on file with the Office of the Secretary of State.
2. Electrical installations in locations classified as hazardous in Article 500 of the National Electrical Code (1990 edition) incorporated herein by reference and on file with the Office of the Secretary of State.
Electrical Code 3. Electrical installations in locations classified as hazardous in Article 500 of the National (1990 edition) with the exception of gasoline dispensing or repair garages.
4. A registrant shall design an alarm or signaling system that is required for life safety or code compliance.
Ref: IBC sec 107, NEC
09/08/2015 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: 5350 E. Speedway Blvd, Propane tank install
T15BU00938
Building Plan (1st Review)

TRANSMITTAL DATE: September 8, 2015

1. The tank location plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Provide a copy of the last approved site plan with your next submittal.

3. Until the above comments have been addressed and all other PDSD review agencies have approved the tank location plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

Final Status

Task End Date Reviewer's Name Type of Review Description
09/10/2015 KROBLES1 OUT TO CUSTOMER Completed