Permit Number: T15BU00920
Parcel: 10711142A

Address:
3100 N ORACLE RD

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T15BU00920
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/19/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/04/2015 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments on the authorized repair submittal for COT ID# 495 at 3100 North Oracle Road. (T15BU00920).


Sheet 1 of 2


No comments.


Sheet 2 of 2


1. In 1st and 2nd paragraphs of Scope of Work, provide references to removal and replacement Z-clips.


2. In 2nd paragraph of Scope of Work, two entirely separate steps are described and should be split into two.


3. Provide standard detail or otherwise describe number and locations of existing and replacement fasteners attaching Z-clips to metal stringers.


4. In South Sign Face Elevation, provide horizontal measurements from outer riser beam centerlines to outside edges of existing and replacement wood face panel sections.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/19/2015 EGALLET1 APPROVAL SHELF Completed
11/19/2015 EGALLET1 OUT TO CUSTOMER Completed
11/19/2015 EGALLET1 REJECT SHELF Completed