Permit Number: T15BU00797
Parcel: 10922003K

Address:
5600 E RIVER RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T15BU00797
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/12/2015 ANDREW CONNOR NPPO REVIEW Passed
10/19/2015 STEVE SHIELDS ZONING REVIEW Approved
10/23/2015 CLAYTON TREVILLYAN BUILDING-COMMERCIAL REVIEW Completed
10/23/2015 ELIZABETH LEIBOLD ENGINEERING REVIEW Approved Tec Man.2-01.4.1.C: Provide Geotechncial Engineering report that includes recommendations for proposed wall & slope design.
10/23/2015 ELIZABETH LEIBOLD ENGINEERING REVIEW Approved The specific retaining wall and associated slope design appears to need more clarification for the key-ins and benching requirements. Please provide an addendum from Western Tech that provides a statement that the proposed retaining wall in conjunction with the SEC slope construction meet the geotechnical requirements, and clarify & revise retaining wall/slope design as needed based on geotechnical recommendations of the addendum. [Tec Man.2-01.4.1.C]
10/23/2015 ELIZABETH LEIBOLD ENGINEERING REVIEW Approved Based on clarification with email/phone conversations with the Geotechnical Engiener, PDSD Engineering is recommending approval of this retaining system permit application. - Elizabeth Leibold, P.E. 26OCT15