Permit Number: T15BU00797
Parcel: 10922003K

Address:
5600 E RIVER RD

Review Status: Completed

Review Details: WALLS - SUBMITTAL

Permit Number - T15BU00797
Review Name: WALLS - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/23/2015 ANDREW CONNOR NPPO REVIEW Reqs Change Submit a copy of the approved and/or revised development package including landscape plan indicating the location of retaining wall for reference. The application will be reviewed for compliance only when the approved documents are included in the submittal.

Ensure that all Zoning and Engineering comments and concerns are addressed.
07/29/2015 MICHAEL ST. PAUL ZONING REVIEW Reqs Change These plans only have sheets 17, 18 and 19 from a set of 19. Provide the full set and a copy of the development package this wall plan is related to.
08/03/2015 CLAYTON TREVILLYAN BUILDING-COMMERCIAL REVIEW Reqs Change BUILDING PLAN
REVIEW COMMENTS
Date: 8-3-15
Activity: T15BU00797
Address: 5600 E River
Applicant: Heather Roberts

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Building Code and local amendments. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions and concerns before permit approval.

1. Provide a site plan that designates the location of the proposed walls on the property, 107.2.

If you have any questions please contact:
Clayton Trevillyan, CBO
520.837.4913
Clayton.Trevillyan@tucsonaz.gov
08/06/2015 ELIZABETH LEIBOLD ENGINEERING REVIEW Reqs Change Retaining wall design does not meet geotechnical engineering recommendations in Technical Manual Section 2-01.9.3 for setback and slope height - needs to be re-designed. See additional comments in DP15-0062. - E Leibold P.E.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/06/2015 EGALLET1 OUT TO CUSTOMER Completed