Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T15BU00768
Parcel: 10711142A

Address:
3100 N ORACLE RD

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T15BU00768
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/14/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
07/30/2015 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments on the authorized electrical repair submittal for COT ID# 495 at 3100 North Oracle Road (T15BU00768).


Sheet 1 of 2


No comments


Sheet 2 of 2


1. In 1st paragraph of Scope of Work and Partial Site Plan, overhead duplex is designated as existing where it is not; provide basis for new installation where prior installation was removed at time demolition permit was pending.


2. In 2nd & 7th paragraphs of Scope of Work respectively indicate weatherhead removal and either reinstallation or installation of appropriate new.


3. In 7th paragraph of Scope of Work, ¾" replacement GRC riser is indicated, while New Electrical Riser Diagram shows 1" replacement EMT; resolve this conflict.


4. Add standard electrical note: any excess fixtures, conduit, connections, wiring, or breakers, no longer being used to be removed.


5. Add standard electrical note: no junction boxes or other fixtures where wire connections are made shall be added or replaced other than those shown on the plan.


6. Add note to clarify that time control enclosure depicted in manufacturer's literature not to be placed inside of the 206PROG panel.


7. In Panel Schedule, the v-a for each lighting circuit is greatly understated and should be close to 1200 v-a and for time clock is substantially overstated; revise to more accurately reflect these loads.


8. In South Sign Face Elevation (or added detail), depict location of first junction box where existing and replacement EMT conduit& wiring is to be disconnected and reconnected; also depict location of existing ballasts and indicate to remain.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/11/2015 AROMERO4 OUT TO CUSTOMER Completed