Permit Number: T15BU00590
Parcel: 99999999S

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T15BU00590
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/03/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/24/2015 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments on the authorized electrical repair submittal for COT ID# 303 at 1456 South Alvernon Way (T15BU00590).


Sheet 1 of 2


1. In aerial overlay site plan, provide dimensions setting location of billboard relative to property lines.


Sheet 2 of 2


1. In 4th paragraph of Scope of Work, Electrical Riser Diagrams & South Face Sign Elevation, revise replacement for underground feed riser conduit to show like or, alternatively, provide justification for proposed change per NEC or utility company requirements.


2. In 6th paragraph of Scope of Work, delete reference to “like”.


3. Add work on ground rods and wire to Scope of Work and clarify if ground rods and wire are to be replaced or added.


4. Provide explanation as to why 122 panel is shown as ballast enclosure rather than ballast enclosures available from ballast manufacturer that are more comparable to existing; clarify if existing 122 panel on billboard is proposed to be used.


5. Provide manufacturer’s cut-sheet for proposed replacement ballast on plan sheet.


6. In One-Line Diagram, correct reference to overhead service.


7. In New Electrical Riser Diagram, correct model number for the proposed ballasts.


8. Add standard note regarding removal of light fixtures from site (replicate Billboard Note #11 on Sheet 1).


9. Add standard note: “There shall be no lighting installation, removal, relocation, or repair, except as noted in Scope of Work”.


10. In Title Block, refer to proposed work as Authorized Electrical Repair.


11. In Title Block, correct number of sign faces.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/04/2015 AROMERO4 OUT TO CUSTOMER Completed