Permit Number: T15BU00579
Parcel: 107142730

Address:
2424 N STONE AV

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T15BU00579
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET 1: NO PROJECT VALUATION GIVEN ON DRAWING. PLEASE PROVIDE.
06/23/2015 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments on the authorized electrical repair submittal for COT ID# 400 at 2424 North Stone Avenue (T15BU00579).


Sheet 1 of 2


!. In Billboard Note #3, add the valuation of the proposed work.


Sheet 2 of 2


1. Resolve conflict between 7th paragraph of Scope of Work and the two Electrical Riser Diagrams/South Face Elevation as to whether ¾" EMT from meter socket box to weatherhead is to be removed and reinstalled or to be replaced with like new.


2. In 9th paragraph of Scope of Work, clarify if ground rods and wire are to be replaced or added.


3. Relocate box on manufacturer's literature for ET8000 Series to reflect correct timer (ET8015CR).


4. Provide manufacturer's literature for the D221N disconnect specified in Scope of Work, rather than that for D221NRB (D221N has been specified in past comparable work, such as T12EL00763, and any upgrade would need to be justified as NEC requirement); revise model numbers indicated in the two Electrical Riser Diagrams, South Face Elevation, and One-Line Diagram accordingly.


5. Add standard note regarding removal of light fixtures from site (replicate Billboard Note #11 on Sheet 1).


6. Add standard note: "There shall be no lighting installation, removal, relocation, or repair, except as noted in Scope of Work".


7. In Title Block, refer to proposed work as Authorized Electrical Repair.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/19/2015 CPIERCE1 OUT TO CUSTOMER Completed