Permit Number: T15BU00434
Parcel: 134031450

Review Status: Completed

Review Details: POOL - COMM MODEL

Permit Number - T15BU00434
Review Name: POOL - COMM MODEL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/18/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/18/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
05/18/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change #1.Please provide a complete electrical plan, show all grounding and bonding, conduits,feeders for ALL equipment including the pool, as requested per last reviews and Electrical Permit Requirements handout information.
#2. One line diagram to include ALL panel schedules, panel schedules to be complete, bus rating, loads to be balanced between phases, AIC rating, circuit numbers, load calc's.
Ref: IBC sec. 107.2.1, NEC art. 110, 408.
05/20/2015 KROBLES1 FIRE REVIEW Needs Review