Permit Review Detail
Review Status: Completed
Review Details: POOL - COMM MODEL
Permit Number - T15BU00434
Review Name: POOL - COMM MODEL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/18/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
05/18/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
05/18/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | #1.Please provide a complete electrical plan, show all grounding and bonding, conduits,feeders for ALL equipment including the pool, as requested per last reviews and Electrical Permit Requirements handout information. #2. One line diagram to include ALL panel schedules, panel schedules to be complete, bus rating, loads to be balanced between phases, AIC rating, circuit numbers, load calc's. Ref: IBC sec. 107.2.1, NEC art. 110, 408. |
05/20/2015 | KROBLES1 | FIRE | REVIEW | Needs Review |