Permit Review Detail
Review Status: Completed
Review Details: POOL - COMM MODEL
Permit Number - T15BU00434
Review Name: POOL - COMM MODEL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/22/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide complete electrical plans per City of Tucson plan submittal requirements for Electrical service and all associated pool equipment. Include grounding and bonding, feeders, load calc's, fault currents. Ref; IBC 107.2.1, NEC 110.3 |
| 04/22/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Replot the drawings for legibility. |
| 04/22/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Replot the drawings for legibility. 2. Revise the size of the gas main per Table 402.4(2), 2012 IFGC or provide calculations to show that the pipe size is correct. |
| 04/22/2015 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 04/22/2015 | LMAKUS1 | ZONING | REVIEW | Passed | |
| 05/04/2015 | KROBLES1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |