Review Details: BILLBOARD - BLDG30days
Permit Number - T15BU00269
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/29/2016 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Reqs Change | The following comments are from the BRC. Below are comments on the authorized repair submittal for COT ID# 400 at 2424 North Stone Avenue (T15BU00269). Sheet 1 of 3 No comments. Sheet 2 of 3 1. In 1st boxed note below Scope of Work, add offset beams to I-beams and upright tapers. 2. In South Face Elevation, indicate west offset beam to be removed and reinstalled rather than removed and replaced (consistent with other revisions made on balance of plan). Sheet 3 of 3 1. Add light support arm mounting clip detail. 2. In Poster Panel Side View, depict light fixture and light fixture support arms and show number and points of attachment of light fixture support arm mounting clips. FIN. |