Review Status: Completed
Review Details: BILLBOARD - BLDG30days
Permit Number - T15BU00256
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/01/2016 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Passed | The following comments are from the BRC. Below are comments on the authorized repair second resubmittal for COT ID# 496 at 2984 North Oracle Road (T15BU00256). Note that the engineer’s responses to Comment #3 on Sheet 2 and Comment #1 on Sheet 3 of the first resubmittal that the number of panel clips is 36 per face is not concurred with; however, the addition of the note on Sheet 2 of the second resubmittal that any panel clips not depicted in the detail on Sheet 3 shall be removed and not reinstalled adequately addresses both of the comments. Sheet 1 of 3 No comments. Sheet 2 of 3 No comments. Sheet 3 of 3 No comments. FIN. |