Review Details: PIA - SUBMITTAL

Plan Number - T14PI00010
Review Name: PIA - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2015 JOSE ORTIZ DOT TRAFFIC REVIEW Approv-Cond January 06, 2015


SUBJECT: Vail Christian Church

PROJECT REVIEWER: Simon Ramos, EIT, Traffic Engineering, City of Tucson DOT

The Signing and Striping Section has completed the reviewed of the PIA plan and recommends a conditional approval of signing and striping plans. The following comments need to be addressed prior to submittal of the mylar plan set for signatures.

1. Include/complete the plan number "I-2014-010" in the title block of each sheet.

2. Include Development Services Department PIA activity number "T14PI00010 on cover sheet.

3. On page 3 of 4, EDIT Striping and Signing Notes as per red -lines.

4. On page 3 of 4, both "R3-5F" signs are to be on top of "R3-5R" signs.

5. On page 3 of 4, REMOVE all "R1-1" signs.

6. On page 3 of 4, ADD "No Left Turn" sign, "R3-5R" sign, and PVC post as per red-lines.

7. On page 3 of 4, ADD street names on plan.


Please Refer to redline plans for additional comments and comment details.

If you have any questions, I can be reached at 837-6678 or Simon.Ramos@tucsonaz.gov



Simon Ramos, E.I.T.
Engineering Associate
Traffic Engineering
Department of Transportation
01/07/2015 LINZUNZA PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSSADOR Completed
01/07/2015 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Denied More time is needed for review.
01/07/2015 LINZUNZA PIA COORDINATOR OUT TO CUSTOMER Completed
12/01/2014 LINZUNZA UTILITY CLEARANCES COT STREETS DIVISION Denied
12/01/2014 LINZUNZA UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Denied
12/01/2014 LINZUNZA UTILITY CLEARANCES PC WASTEWATER MGMT Denied
12/01/2014 LINZUNZA UTILITY CLEARANCES QUEST COMMUNICATION Denied
12/01/2014 LINZUNZA UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Denied
12/01/2014 LINZUNZA UTILITY CLEARANCES COX COMMUNICATION Denied
12/01/2014 LINZUNZA UTILITY CLEARANCES SOUTHWEST GAS CORP Denied
12/01/2014 LINZUNZA UTILITY CLEARANCES EL PASO NATURAL GAS Denied
12/01/2014 LINZUNZA UTILITY CLEARANCES KINDER MORGAN ENERGY Denied
12/16/2014 GARY WITTWER DOT LANDSCAPE REVIEW Approv-Cond It appears that there is no landscape or irrigation within the ROW. Correct?
Detail Fon sheet 4 of 4. We do not want this area for landscaping, please concrete in the porkchop.
12/30/2014 RICHARD LEIGH DOT ENGINEERING REVIEW Denied Comments by Craig Saltzman, 520-837-6621
Craig.Saltzman@tucsonaz.gov


1) Sht. 4 of 4 AC Paving Section
Use 2' Mix #3 0n 2' Mix #1 on 8 1/2 " ABC
See Interim Structural Section Sht. 2 of 37 I-87-021 Valencia Rd. (Phase I) Kolb Rd. to Houghton RD. (attached)

Pg. 4 Vail Christian Church : Soils Report
Compressive properties 1st paragraph second sentence:
"However, at increased moisture contents we expect that the soils will exhibit moderate additional compression or collapse."

2) Sht. 4 of 4 West Entrance Detail
A. Add 6 ft. wide pedestrian access w/curb across traffic island.
B. Change 6 inch type vertical curb to 8 inch

3) Sht. 4 of 4 Thickened Edge
A. 9 inch thickness change to 12 inch
B. 12 inch width change to 24 inches

4) sht 4 of 4 West Entrance
A. Storm Sewer MH and pipe relocate both to be within City R/W
B. Existing design 24" RCP 90 degrees to 38" X 24" HERCP - Address Angle of Confluence
100 yr Q 24 RCP =97 cfs
100 yr Q main line 24 RCP up stream of MH =27 cfs
Exist 24 RCP is a lateral joining the main line 38 X 24 HERCP using a MH
The angle of confluence needs to addressed see the following from Storm Sewer Design Manual

Reference
Storm Sewer Design Manual
Section 4. "Angle of confluence, A , shall be less than or equal to 45 degrees w/ 45 degrees perfered except that A shall be less than 30 degrees for the following:
a) Q in greater than 10 percent of Q mainline.
b) Qin has velocity greater than 20 fps.
c) Diameter (d) of laternal is 60 inches or more."