Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T14OT00875
Parcel: 117060620

Address:
238 N 4TH AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14OT00875
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/15/2016 LOREN MAKUS ENGINEERING REVIEW Reqs Change The parcel will largely be removed from the 1-percent flood hazard area at the effective date of the proposed LOMR, June 13, 2016. If the applicant wishes to wait until the effective date for permit issuance, the following comments will not apply.

a. On the site plan show floodplain information including a notation the entire project is within a FEMA zone AE. (AM 2-06.4.8.I)
b. Provide water surface contours at the upstream and downstream ends of the project site. (AM 2-06.4.8.I)
c. Provide finish floor elevations for each structure on the site. The FFE for each structure must be at the regulatory flood elevation, one foot above the base flood elevation.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/19/2016 KROBLES1 OUT TO CUSTOMER Completed