Permit Number: T14OT00680
Parcel: 13014439B

Address:
4426 E 22ND ST

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T14OT00680
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/13/2014 ELIZABETH EBERBACH ENGINEERING REVIEW Denied Drainage report proposes EHS based on eqn 7.8b however the City gets a different ratio of radius of curvature to Top width that is closer to 3.5; equation 7.8c should be used. Also, drainage report is missing TDOT approved design of bank protection required per Rezoning condition. Proposed FFE for proposed building is lower than adjacent FEMA BFE's and needs to be revised. Additional drainage related comments will be posted under the review for DP14-0089 after site plan review is completed. [Ref: Tech Man Sections: 4-04.7.6.1, 4-04.2.2, Tuc Code 26-5.2(9)]

Final Status

Task End Date Reviewer's Name Type of Review Description
07/02/2014 FERNE RODRIGUEZ OUT TO CUSTOMER Completed