Permit Review Detail
Review Status: Completed
Review Details: OTHER - BLDG ONLY
Permit Number - T14OT00197
Review Name: OTHER - BLDG ONLY
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/17/2015 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 600 IDF 1. OK CENTRO STERILE RODI WATER TREATMENT 2. OK COOLING TOWER 2 3. This project includes structural concrete structure design, metal building foundation design and metal building. a. Please provide copy of permits and special inspectors reports obtained for this structural work. 4. PR#2 Drawings for Central Plant Concrete Pit Enlargement S1.1, S2.1 and S2.3 are included as part of the Cooling Tower Project. a. Should this have been a separate project from the cooling tower? b. Please provide copy of permits and special inspectors reports obtained for this structural work. TMC CENTRAL STERILE 5. This project includes structure design componants. a. Please provide copy of permits and special inspectors reports obtained for this structural work. TMC LAUNDRY SHAKER BIPASS 6. OK TMC PBX COOLING 7. The weight of the blower coil units was not provided in the mechanical schedule. Were structural analysis and calculations completed for the existing roof framing members and the coil suspension brackets? a. Provide copy of the building permit. TMC SHOP BUILDING SINK 8. OK WOMEN'S CENTER SUGERY O.R. 9. OK END OF REVIEW |