The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T14OT00195
Parcel: 13314227C

Address:
1400 N WILMOT RD

Review Status: Completed

Review Details: OTHER - BLDG ONLY

Permit Number - T14OT00195
Review Name: OTHER - BLDG ONLY
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/09/2015 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change As per the City of Tucson Amendments to the 2012 International Building Code, Section 105.1.1 Annual Permits the following work shall not be covered within the scope of the annual permit and shall require separate permitting:
1. Any work creating a different occupancy group for all or any portion of a building.
2. Any work creating a different building type for all or any portion of a building.
3. Any work that adds, alters, removes or penitrates rated fire or smoke control assemblies, exits courts, exit passegageways or horizontal exits.
4. Any work that provides for the relocation of more than five sprinkler heads.
5. Any work that modifies load bearing structures.

After review of the five projects completed during the 2014 period, it was found that three of these projects are likely to have have at least 5 or more sprinkled heads moved and or modified; Genesis, Geriatric and Ferguson.
a. As per the automatic sprinkler systems note provided on the plumbing drawings of each project, sprinkler modification drawings were to be submitted to the Fire department for their review and approval. Please provide a copy of the fire department review and approval for each project.

Exit passageways on Genesis were modified, altered and added. Was a permit obtained of this work and if so please provide a copy of the final inspection and approval?

END OF REVIEW