Permit Number: T14OT00174
Parcel: 13216600A

Address:
4004 S PARK AV

Review Status: Completed

Review Details: OTHER - BLDG ONLY

Permit Number - T14OT00174
Review Name: OTHER - BLDG ONLY
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/11/2015 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change TARP GAS LINE REPLACEMENT
1. OK
TUCSON WATER LA ENTRADA-GENERATOR REPALCEMENT
Sheet EP101
2. The construction notes state that the general contractor is to determine either a new concrete foundation pad is required for the new generator. Was a new foundation pad provided? Structural modifications require a permit and structural design and calculations. Please reconcile and respond in writing.
TUCSON WATER LA ENTRADA-PATIO REPAIRS
3. Drawing A4.0 is missing
4. No electrical design for installation of new outdoor lighting.
HARRISION FUEL ISLAND-EMERGENCY GENERATOR
5. Sheets E501 and E001 are missing
6. Notes on sheet E601 refer to sheet E501 for details for the generation foundation pad. Structural modifications require a permit and structural design and calculations. Please reconcile and respond in writing.
END OF REVIEW
PLEASE RESOND TO ALL COMMENTS IN WRITING.