Permit Number: T14CM08986
Parcel: 130054980

Address:
2210 E 33RD ST

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T14CM08986
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/12/2015 KEN BROUILLETTE FIRE REVIEW Approv-Cond PLANS NEED TO BE SUBMITTED TO STATE FIRE MARSHAL. PUBLIC SCHOOL
01/22/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET S1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE GENERAL STRUCTURAL NOTES AND THE DETAIL VERBIAGE.
2. SHEET S1; GENERAL STRUCTURAL NOTES (FOUNDATIONS): THE FIRST NOTE INDICATES A SOIL REPORT WAS USED FOR THE FOUNDATION DESIGN. PROVIDE THAT REPORT FOR REVIEW (ONE COPY).
3. GENERAL: PROVIDE TWO SETS OF STRUCTURAL CALCULATIONS.
4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
01/27/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Denied #1.Approval subject to subsequent review due to potential structural changes.
#2.Plan sheet 'E4.1, provide labeling per art. 690.17 NEC .
To be applied on appropriate disconnect switches.
#3.As per keyed note #23 on plan sheets 'E4.0', 'E5.0', 'E5.1' .Please provide acceptable method for line side tap in ses equip. Approved by manufacturer of service equip. so as not to void listing or compromising the performance of the equipment.Optional field evaluation by NRTL.
D Santa Cruz,
Elect. Plans Examiner
520-837-9077

Final Status

Task End Date Reviewer's Name Type of Review Description
01/29/2015 AROMERO4 OUT TO CUSTOMER Completed