Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T14CM08986
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/12/2015 | KEN BROUILLETTE | FIRE | REVIEW | Approv-Cond | PLANS NEED TO BE SUBMITTED TO STATE FIRE MARSHAL. PUBLIC SCHOOL |
| 01/22/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET S1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE GENERAL STRUCTURAL NOTES AND THE DETAIL VERBIAGE. 2. SHEET S1; GENERAL STRUCTURAL NOTES (FOUNDATIONS): THE FIRST NOTE INDICATES A SOIL REPORT WAS USED FOR THE FOUNDATION DESIGN. PROVIDE THAT REPORT FOR REVIEW (ONE COPY). 3. GENERAL: PROVIDE TWO SETS OF STRUCTURAL CALCULATIONS. 4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 01/27/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Denied | #1.Approval subject to subsequent review due to potential structural changes. #2.Plan sheet 'E4.1, provide labeling per art. 690.17 NEC . To be applied on appropriate disconnect switches. #3.As per keyed note #23 on plan sheets 'E4.0', 'E5.0', 'E5.1' .Please provide acceptable method for line side tap in ses equip. Approved by manufacturer of service equip. so as not to void listing or compromising the performance of the equipment.Optional field evaluation by NRTL. D Santa Cruz, Elect. Plans Examiner 520-837-9077 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/29/2015 | AROMERO4 | OUT TO CUSTOMER | Completed |