Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T14CM08935
Parcel: 13707034B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM08935
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2015 MARTIN BROWN FIRE REVIEW Approved
01/13/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET G000.A; PROJECT SUMMARY: REFERENCE IS MADE TO THE IBC TABLE 503 FOR CONSTRUCTION TYPE. THE CONSTRUCTION TYPE SHOULD REFERENCE THE IBC CHAPTER 6, WHILE TABLE 503 IS FOR ALLOWABLE BUILDING HEIGHTS AND AREAS.
2. SHEET G000.A; PROJECT SUMMARY: REFERENCE IS MADE TO THE IPC TABLE 4-1 FOR REQUIRED PLUMBING FIXTURES. REVISE THE REFERENCE TO TABLE 403.1 OF THE IPC OR TABLE 2902.1 OF THE IBC.
3. SHEET G000.A; PROJECT SUMMARY: THE OCCUPANT LOAD CALCULATION INDICATES 200 SF/PERSON FOR THE OCCUPANCY DETERMINATION. PER THE IBC TABLE 1004.1.2, USE AN ALLOWABLE SF/OCCUPANT OF 100. REVISE THE DRAWING.
4. SHEET G000.A; PROJECT SUMMARY: INCLUDE IN THE PLUMBING CALCULATIONS THE REQUIREMENTS FOR DRINKING FOUNTAINS (HIGH/LOW OR SINGLE POINT OF USE) AND THE SERVICE SINK.
5. SHEET G000.B; EXIT CALCULATION TABLE; CODE PLAN: THE OCCUPANT LOAD INDICATED IN THE TABLE IS 70. COORDINATE THE TOTAL OCCUPANT LOAD TO THAT SHOWN ON SHEET G000.A.
6. SHEET A101; PARTIAL FLOOR PLAN AND PARTITION DEMOLITION PLAN: PROVIDE A NORTH ARROW ON THE PLANS.
7. SHEET A101; SLAB REPAIR DETAIL 20: INDICATE ON THE PLAN THE LOCATION OF THIS REPAIR.
8. SHEET A101; DEMOLITION PLAN GENERAL NOTES: DARKEN THE NOTES.
9. SHEET A101; FLOOR PLAN KEY NOTES: NOTES 3.3, 3.5, 3.6, 3.7, 4.4, AND 15.2 WERE NOT LOCATED ON THE PLAN. VERIFY.
10. SHEET A111; REFLECTED CEILING KEYNOTES: THERE ARE MANY REFLECTED CEILING PLAN KEYNOTES LISTED ON THIS SHEET THAT WERE NOT LOCATED ON THE PLAN. VERIFY.
11. SHEET A400: THERE ARE MANY ELEVATION KEYNOTES LISTED ON THIS SHEET THAT ARE NOT SPECIFIC TO THIS PROJECT. REMOVE THOSE NOTES AS REQUIRED.
12. SHEET A510; DETAIL 21B: INDICATE THE KICKER SIZE AND SPACING (OR REFERENCE DETAIL 9B).
13. SHEET A510; DETAIL 2 (INTERIOR METAL STUD SCHEDULE): THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE.
14. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
01/20/2015 ROBERT SHERRY WATER REVIEW Completed
01/20/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
01/20/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
01/26/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Denied #1.Please provide the AIC rating on panel 'L4'.
#2. Designate circuiting for luminaires.
#3. General note on plan allowing the use of mc cable should address ART.517.13 NEC.
D Santac Cruz, Elect. Plans Examiner
520-837-4995

Final Status

Task End Date Reviewer's Name Type of Review Description
02/02/2015 SHANAE POWELL OUT TO CUSTOMER Completed
02/02/2015 CPIERCE1 REJECT SHELF Completed