Permit Number: T14CM08917
Parcel: 140060720

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM08917
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/18/2015 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Reqs Change Date: 4-21-15
Activity: T14CM08917
Address: 5433 S Madison #2
Applicant: Jesus Antonio Jauregui

Note: The following comments have not been addressed. A meeting with the plan reviewer, designer and property owner may be scheduled to clarify these comments by contacting the reviewer specified below.

PREVIOUS COMMENTS:
1. Specify the location of all utility lines and service meters including those supplying the existing building, R106.1.1. Note: the electrical, water and gas lines to the existing residence have not been specified.
2. Show the mechanical unit and its working platform on the elevation drawings, M1305.1. Note: roof mounted equipment must have a working platform when the roof has a pitch of 3:12 or greater.

If you have any questions please contact: