Permit Number: T14CM08910
Parcel: 10509550A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM08910
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/29/2014 DAVID RIVERA ZONING REVIEW Approved
12/29/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
12/29/2014 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
12/29/2014 ROBERT SHERRY WATER REVIEW Completed
12/29/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/29/2014 RSHERRY1 WWM REVIEW Passed No water meter size change.
12/29/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The temperature mixing valve is not being installed per the manufacturer's instructions; it is designed for single-faucet installations. In addition, the remarks in the plumbing fixture schedule list ASSE 1016, 1017, and 1069 as being acceptable. Only ASSE 1070-listed mixing valves are acceptable for lavatories in public restrooms.
2. Revise the water supply isometric to show the lavatories plumbed with the hot water outlet on the left and the cold water outlet on the right.
3. Show the size, route, and temination points for the condensate drains for the rooftop units.
12/29/2014 JASON GREEN ENGINEERING REVIEW Approved
12/29/2014 MARTIN BROWN FIRE REVIEW Approved
12/29/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed