Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM08910
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/29/2014 | DAVID RIVERA | ZONING | REVIEW | Approved | |
12/29/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
12/29/2014 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
12/29/2014 | ROBERT SHERRY | WATER | REVIEW | Completed | |
12/29/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
12/29/2014 | RSHERRY1 | WWM | REVIEW | Passed | No water meter size change. |
12/29/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The temperature mixing valve is not being installed per the manufacturer's instructions; it is designed for single-faucet installations. In addition, the remarks in the plumbing fixture schedule list ASSE 1016, 1017, and 1069 as being acceptable. Only ASSE 1070-listed mixing valves are acceptable for lavatories in public restrooms. 2. Revise the water supply isometric to show the lavatories plumbed with the hot water outlet on the left and the cold water outlet on the right. 3. Show the size, route, and temination points for the condensate drains for the rooftop units. |
12/29/2014 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
12/29/2014 | MARTIN BROWN | FIRE | REVIEW | Approved | |
12/29/2014 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |