Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T14CM08873
Parcel: 10714233A

Address:
244 W GRANT RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM08873
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/24/2014 CARL SCHULTZ FIRE REVIEW Approved
12/24/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Demonstrate energy code compliance for the alterations to the building envelope based on the current code. Reference: Sections C101.4.3, C101.5, and C103.2, International Energy Conservation Code 2012.
2. Alterations of an existing building in which the existing ceiling or wall cavities are exposed, shall have the exposed cavities filled with insulation. Reference: Section 101.4.3, IECC 2012.
3. Provide NFRC fenestration product ratings for the U-factor on COMcheck or use the appropriate default U-factor from Table C303.1.3 (1), IECC 2012. Show the required U-factors for the vertical glazing on the drawings. Reference: Section C303.1.3, IEC 2012.
4. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012.
12/24/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
12/24/2014 ROBERT SHERRY WATER REVIEW Completed
12/24/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET T1.1; EGRESS/OCCUPANCY PLAN: THE OCCUPANT LOAD INDICATES USAGE OF A WAREHOUSE AND OFFICE, WHILE THE BUILDING IS LISTED AS MERCANTILE. REVISE THE OCCUPANCY CALCULATION FOR OFFICE, WAREHOUSE, AND RETAIL USE.
2. SHEET T1.1; EGRESS/OCCUPANCY PLAN: INDICATE ON THE DRAWINGS IF THE WAREHOUSE AREA IS S-1 OR S-2.
3. SHEET T1.1; EGRESS/OCCUPANCY PLAN: THE NOTE CONCERNING EXIT SIGNS MIGHT CHANGE IF TWO EXITS ARE REQUIRED IN THE SALES/OFFICE AREA.
4. SHEET T1.1; PLUMBING FIXTURE ANALYSIS: THE REQUIRED WATER CLOSET/LAVATORIES ARE DETERMINED ON THE DRAWINGS FOR A 'B' OCCUPANCY. REVISE..
5. SHEET A1.1; FLOOR PLAN: DEPENDING ON THE NEW OCCUPANT LOAD IN THE SALES/OFFICE AREA, IF TWO EXITS ARE REQUIRED, THE HALLWAY BETWEEN THE BREAK ROOM AND RESTROOMS WILL HAVE TO BE FIRE RATED. VERIFY AND REVISE WALL TYPE ON A1.1 AS REQUIRED.
6. SHEET A1.1; FLOOR PLAN: IN THE RECEPTION ROOM, CLEAR UP THE WALL TYPE/KEYNOTE CALL-OUTS.
7. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
12/24/2014 JASON GREEN ENGINEERING REVIEW Approved
12/24/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/31/2014 SPOWELL1 WWM REVIEW Needs Review
12/31/2014 SPOWELL1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
12/31/2014 SPOWELL1 ZONING REVIEW Needs Review