Permit Number: T14CM08849
Parcel: 116183320

Address:
450 N GRANDE AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM08849
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/17/2015 MICHAEL ST. PAUL ZONING REVIEW Approved
03/17/2015 JASON GREEN ENGINEERING REVIEW Approved
03/18/2015 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Completed
03/18/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
03/18/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
03/18/2015 KEN BROUILLETTE FIRE REVIEW Approved
03/18/2015 ROBERT SHERRY WATER REVIEW Completed
03/19/2015 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change SHEET A1
1. Please provide cut sheets and specifications for intumescent paint as stated in Note "R".
2. Need a fire rated shutter with automatic closure over opening from Game Room 107 to Corridor 104.
3. Door "F" from 107 to 100 must be rated and have panic hardware.
4. Insure panic hardware on all doors as required by the 2012 IBC, Section 1008.1.10.
5. Note "R" reference for the interior fire rated wall must state "for both interior sides" not for interior and exterior sides.
6. Please provide south and west exterior elevations showing parapets, no parapets and window locations and sizes.
END OF REVIEW
03/19/2015 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved