Permit Number: T14CM08841
Parcel: 10509550A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM08841
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/09/2015 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change Because the original tenant is divided into two tenant spaces, there must therefore be two new addresses for the two new tenant spaces. With two new addresses, two building permits must be obtained for construction.
01/14/2015 ROBERT SHERRY WATER REVIEW Completed
01/14/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
01/14/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
01/23/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change #1 .Provide for rooftop GFI maintenance receptacle for new rooftop RTU #4.
#2. Circuiting not designated for new type 'S' egress fixtures.
#3.No panel schedule for panel 'A' plan sheet 'E3'
#4. Provide compliance of Tucson Outdoor Ltg code.


Circuiting not designated for new type 'S' egress lighting.
D Santa Cruz
520-837- 9077
12/29/2014 MARTIN BROWN FIRE REVIEW Approved