Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM08841
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/09/2015 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Because the original tenant is divided into two tenant spaces, there must therefore be two new addresses for the two new tenant spaces. With two new addresses, two building permits must be obtained for construction. |
| 01/14/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 01/14/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 01/14/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 01/23/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | #1 .Provide for rooftop GFI maintenance receptacle for new rooftop RTU #4. #2. Circuiting not designated for new type 'S' egress fixtures. #3.No panel schedule for panel 'A' plan sheet 'E3' #4. Provide compliance of Tucson Outdoor Ltg code. Circuiting not designated for new type 'S' egress lighting. D Santa Cruz 520-837- 9077 |
| 12/29/2014 | MARTIN BROWN | FIRE | REVIEW | Approved |