Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T14CM08825
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/20/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
03/23/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Revise the mechanical compliance certificate to indicate that high efficiency HVAC is being used to address the requirements of Section C406, IECC 2012. [Second comment: The submitted COMcheck Mechanical Compliance Certificate includes only five of the seven HVAC systems for the building. In addition, the architect has selected "high efficiency HVAC" (Section C406.2, IECC 2012) as the required additional efficiency package for this activity; revise the COMcheck Mechanical Compliance Certificate to coordinate this with the architect.][Initial comment: The submitted COMcheck Mechanical Compliance Certificate is based on the 2009 IECC and shows that HVAC System 1 fails to comply with the code requirements. Submit a revised COMcheck Mechanical Compliance Certificate based on the 2012 IECC that shows all of the HVAC systems in compliance with the current code requirements.] |
03/23/2015 | KROBLES1 | ZONING | REVIEW | Reqs Change |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/23/2015 | KROBLES1 | OUT TO CUSTOMER | Completed |