Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM08802
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/12/2015 | SPOWELL1 | WWM | REVIEW | Needs Review | |
| 12/22/2014 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 12/22/2014 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 12/22/2014 | KEN VAN KARSEN | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | PROVIDE EXTERIOR LIGHTS CALC |
| 12/22/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The City of Tucson has not adopted ASHRAE Std. 60.1-2010 for ventilaation calculations. Use the ventilation calculations from Section 403.3, IMC 2012. |
| 12/22/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/22/2014 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 12/22/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide metering water faucets for the lavatories in the restrooms. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson. 2. Provide the specifications for the water heater. Verify that the manufacturer will allow the recirculation of hot water as shown on detail 1/P-2. |
| 12/22/2014 | CARL SCHULTZ | FIRE | REVIEW | Denied | Per IFC and IBC table 1018.1 all corridors shall be 1 hour fire rated and all doors shall be 20 min fire rated self closing and self latching. |
| 12/22/2014 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |