Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Permit Number - T14CM08784
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/10/2015 | KROBLES1 | BUILDING-RESIDENTIAL | REVIEW | Needs Review | |
| 12/19/2014 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 12/23/2014 | STEVE SHIELDS | ZONING | REVIEW | Denied | P&DS TRANSMITTAL FROM: Steve Shields, Lead Planner PROJECT: T14CM08784 2317 N. Martin Avenue Enclose carport to two (2) bedrooms and bath TRANSMITTAL: December 23, 2014 COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1). The property is zoned NR-1. Neighborhood Preservation Zone (NPZ) review is required. This site is located in the R-1 zone (UDC 4.7.8). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A). Based on a will height of 14'-0" the required perimeter yard setback to the north property line is 9'-4", proposed is 6'-0". |
| 12/23/2014 | SSHIELD1 | NPPO | REVIEW | Passed |