Permit Number: T14CM08778
Parcel: 11304112B

Address:
3448 N 1ST AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM08778
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/02/2015 MARTIN BROWN FIRE REVIEW Approved
06/02/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
06/02/2015 JASON GREEN ENGINEERING REVIEW Approved
06/02/2015 ROBERT SHERRY WATER REVIEW Completed
06/02/2015 STEVE SHIELDS ZONING REVIEW Approved
06/02/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Comment not resolved. [Initial comment: Revise the mechanical design as required to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2012.]
2. Up date the COMcheck with the NFRC numbers. [Initial comment: Demonstrate energy code compliance for the addition to the building envelope using calculations based on the current code. Reference: Sections C101.4.3, C101.5, and C103.2, International Energy Conservation Code 2012.]
3. Comment not addressed. [Initial comment: Provide NFRC fenestration product ratings for the U-factor and the SHGC values on COMcheck or use the appropriate default U-factor and SHGC values from Tables C303.1.3 (1), C303.1.3 (2) and C303.1.3.(3), IECC 2012. Reference: Section C303.1.3, IECC 2012.]
06/02/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved