Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T14CM08778
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/02/2015 | MARTIN BROWN | FIRE | REVIEW | Approved | |
06/02/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
06/02/2015 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
06/02/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
06/02/2015 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
06/02/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Comment not resolved. [Initial comment: Revise the mechanical design as required to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2012.] 2. Up date the COMcheck with the NFRC numbers. [Initial comment: Demonstrate energy code compliance for the addition to the building envelope using calculations based on the current code. Reference: Sections C101.4.3, C101.5, and C103.2, International Energy Conservation Code 2012.] 3. Comment not addressed. [Initial comment: Provide NFRC fenestration product ratings for the U-factor and the SHGC values on COMcheck or use the appropriate default U-factor and SHGC values from Tables C303.1.3 (1), C303.1.3 (2) and C303.1.3.(3), IECC 2012. Reference: Section C303.1.3, IECC 2012.] |
06/02/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |