Permit Number: T14CM08771
Parcel: 11716029A

Address:
103 E ALAMEDA ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM08771
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/07/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET g2.0; FLOOR PLAN; OCCUPANT LOAD: THE FLOOR PLAN INDICATES 51 OCCUPANTS IN COURTROOM 1 (35+2+14), THE OCCUPANT LOAD ANALYSIS INDICATES 54 OCCUPANTS (PER THE IBC), AND THE ACTUAL OCCUPANT LOAD (FIXED SEATING) INDICATES 49 OCCUPANTS. CLARIFY.
2. SHEET g2.0; CODE ANALYSIS: THE OCCUPANCY SEPARATION IS LISTED AS ONE HOUR BETWEEN THE B AND A-3 AREAS (PER THE IBC TABLE 508.4). DOES THE EXISTING CONSTRUCTION MEET THAT CRITERIA? VERIFY.
3. SHEET g2.0; CODE ANALYSIS: THE TYPE OF CONSTRUCTION REFERENCES TABLE 503 OF THE IBC. REVISE THE REFERENCE TO CHAPTER 6.
4. SHEET g2.0; CODE ANALYSIS: THE 'EXIT WIDTH REQUIREMENT' INDICATES THE REQUIRED/PROVIDED EXIT WIDTHS ARE SHOWN ON THE FLOOR PLAN. PROVIDE.
5. SHEET a1.0; COURT ROOM 1 DEMOLITION PLAN: CLEAR UP NOTE 2.15 ON THE PLAN.
6. SHEET a1.1; KEYNOTES: NOTE 5.01 REFERENCES A DETAIL 4/a6.1. THERE IS NO SHEET a6.1. REVISE.
7. SHEET a1.1; COURT ROOM 1 FLOOR PLAN: IF NEW WALLS ADDED IN THIS TENANT IMPROVEMENT ARE REQUIRED TO BE RATED, LIST THE U.L. NUMBER FOR THAT WALL ON THE WALL SECTION, OR THE PRESCRIPTIVE ASSEMBLY AS ADDRESSED IN THE IBC SECTION 721.
8. SHEET a3.0; ELEVATION 3: CLEAR UP THE DETAIL/KEYNOTE INDICATORS ON THE RIGHT SIDE OF THE ELEVATION.
9. SHEET a5.1; SECTION 2: THE DIAGONAL BRACE IS NOTED 'WHERE REQUIRED'. INDICATE WHERE THE BRACES ARE REQUIRED.
10. SHEET a5.1; SECTION 4: INDICATE THE ANCHORS WILL BE EXPANSION ANCHORS, AND PROVIDE THE ANCHOR EMBEDMENT LENGTH INTO THE SLAB.
11. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
01/15/2015 ROBERT SHERRY WATER REVIEW Completed
01/15/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
01/15/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
01/23/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change #1 Please designate : new ,used, existing, for light fixtures, also circuiting, incude for all recepacles.
#2 Panel schedules to reflect circuiting, loads.
Per IBC 107.2.1, and art.210 NEC, COT Plan Submittal Requirements.
D Santa Cruz ,Elect.Plans Examiner
520-837-9077
12/23/2014 AROMERO4 WWM REVIEW Passed No water meter size change.
12/29/2014 MARTIN BROWN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/05/2015 SHANAE POWELL OUT TO CUSTOMER Completed
02/05/2015 CPIERCE1 REJECT SHELF Completed