Permit Number: T14CM08763
Parcel: 117042530

Address:
131 E 6TH ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM08763
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/12/2015 AROMERO4 FIRE REVIEW Needs Review
01/12/2015 AROMERO4 WWM REVIEW Completed
12/19/2014 JASON GREEN ENGINEERING REVIEW Approved December 19, 2014
FLOODPLAIN USE PERMIT NO.: T14OT01590
ADDRESS: 131 E 6th St Tucson, Arizona 85705
PROPERTY OWNER: Quattro Ninos LLC

The applicant is authorized to use a portion of the FEMA Special Flood Hazard Area Zone AE floodplain per the Flood Insurance Rate Maps 04019C2276L, specifically described as: A portion of Parcel 124-07-0850.
For the purpose of a tenant improvement to an existing non-conforming Historic Building.

The applicant agrees to comply with City of Tucson Floodplain and Erosion Hazard, and Watercourse Amenities, Safety and Habitat regulations, and is particularly bound by the conditions stated below. Violation of any of the conditions stated or referred to below, as determined by the City Engineer, shall be grounds for revocation of this permit. Responsibility for renewal of this permit, if necessary, is with the applicant. Issuance of this permit does not constitute a waiver of other requirements contained in the Tucson City Code, Unified Development Code, or any other Federal, State, or local regulation. No use other than as permitted herein is allowed. Additional uses allowed under City of Tucson Floodplain and Erosion Hazard Regulations and Watercourse Amenities, Safety, and Habitat regulations require the issuance of an additional Floodplain Use Permit.

The following conditions shall apply to this permit. (Or refer to Tucson City Code Chapter 26)

1. All work shall conform to the attached plans (T14CM08763) which are made part of this permit.

2. The structure is a contributing structure to the Tucson Warehouse Historic District. All repairs and improvements must be completed in a manner to preserve the historic character of the structure and the historic district and reviewed and approved by the Tucson Historic Preservation Office.

3. The existing drainage patterns at the property lines shall not be obstructed or changed.

4. Except as approved by the City Engineer prior to the start of construction, development under this permit shall not obstruct, retard or divert the existing flow of floodwaters from or to adjacent properties.

5. This permit becomes invalid and is subject to additional floodplain review, if any required development permit changes the configuration of the structure and or site development.

6. Any patio walls to be constructed will require a separate Floodplain Use Permit.

This Floodplain Use Permit will be automatically revoked and becomes invalid if conditions are not complied with, as set forth in this permit.

APPLICANT NAME: MetroTED
ADDRESS: 88 W Cushing St Tucson, AZ 85705
PHONE: 520-990-6866

(EXPIRATION DATE) Month: 12 Day: 19 Year: 2015

SIGNATURE OF APPLICANT DATE

The applicant is authorized by the City Engineer to receive a floodplain use permit subject to the above referenced conditions and restrictions.
12/19/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET a0.1; PROJECT DATA: THE DRINKING FOUNTAIN MUST BE A HIGH/LOW OR SINGLE POINT OF USE DISPENSER (CONNECTED DIRECTLY TO WATER LINE). VERIFY.
2. SHEET a0.2; EXITING PLAN: THE PLAN TITLE INDICATES A BASEMENT. DOES THIS MEET THE DEFINITION OF BASEMENT IN THE IBC CHAPTER 2? VERIFY.
3. SHEET a3.0; FLOOR PLAN: KEY NOTE 7 INDICATES A FRAMED SHELF TO SUPPORT THE WATER HEATER. REFERENCE 38/a9.1.
4. SHEET a3.0; KEY NOTES: NOTE 34 REFERENCES UNISEX TOILET SIGNAGE. VERIFY THE IBC SECTION REFERENCE. IS THIS A UNISEX TOILET?
5. SHEET a3.1; WALL TYPES: WALL TYPES A AND C REFERENCE SHEET a9.2. REVISE.
6. SHEET a9.1; DETAIL 36: THE IBC SECTION 1109.12 REQUIRES A PORTION OF SERVICE COUNTERS (RECEPTION DESK) TO BE ACCESSIBLE (2'-10" MAXIMUM HEIGHT. VERIFY.
7. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
12/19/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/22/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide two drinking fountains (one high, the other low) or a point of use water dispener. reference: Section 410.2, IPC 2012.
12/22/2014 ROBERT SHERRY WATER REVIEW Completed
12/22/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Resolve the disparity between the calculated outside air requirement (1200 CFM) and the outside air scheduled for the heat pumps (1000 CFM).
12/22/2014 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Completed
12/31/2014 MICHAEL ST. PAUL ZONING REVIEW Approved