Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T14CM08635
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/25/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
03/05/2015 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
03/09/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
03/09/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the island venting of hand sink K30 as shown on the waste and vent piping isometric (sheet P4.1) to include the connection of the low point of the vent to the drain, downstream of the fixture drain (see detail on P5.1). Note that a cleanout is required in the vertical section of the vent, prior to the connection of the low point of the vent to the drain (see Section 916.3, IPC 2012). [Second comment: The Pima County Health Department requires hand sinks to be used for hand washing only; provide a direct waste connection.] [Initial comment: Clarify the reason for using indirect waste connections for the pre-rinse sink (K69) and hand sink (K30) and for the soiled dish table (K68). Reference: Section 802.1, IPC 2012.] 2. Only one copy of the revised sheet P2.1 has been submitted. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/13/2015 | SHANAE POWELL | OUT TO CUSTOMER | Completed |
03/13/2015 | CPIERCE1 | REJECT SHELF | Completed |