Permit Review Detail
Review Status: Active
Review Details: COMMERCIAL - TI
Permit Number - T14CM08560
Review Name: COMMERCIAL - TI
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/15/2014 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 12/15/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide heating and cooling load calculations that justify the capacity of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012. 2. Show that the proposed heat pump meets the requirements of Sections C403.2.2, C403.2.3, C403.2, and C403.3 (e.g. provide the mechanical energy code compliance certification from COMcheck). Reference: Section C303.1, International Energy Conservation Code 2012. |
| 12/15/2014 | ANY | ELECTRICAL-COMMERCIAL | REVIEW | Active | |
| 12/15/2014 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 12/15/2014 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/15/2014 | RSHERRY1 | WWM | REVIEW | Passed | No wastewater plumbing. |
| 12/15/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 12/15/2014 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 12/15/2014 | CARL SCHULTZ | FIRE | REVIEW | Approved | |
| 12/15/2014 | RONALD BROWN | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |