Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T14CM08560
Parcel: 13413057D

Review Status: Active

Review Details: COMMERCIAL - TI

Permit Number - T14CM08560
Review Name: COMMERCIAL - TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
12/15/2014 MICHAEL ST. PAUL ZONING REVIEW Approved
12/15/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating and cooling load calculations that justify the capacity of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012.
2. Show that the proposed heat pump meets the requirements of Sections C403.2.2, C403.2.3, C403.2, and C403.3 (e.g. provide the mechanical energy code compliance certification from COMcheck). Reference: Section C303.1, International Energy Conservation Code 2012.
12/15/2014 ANY ELECTRICAL-COMMERCIAL REVIEW Active
12/15/2014 ROBERT SHERRY WATER REVIEW Completed
12/15/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
12/15/2014 RSHERRY1 WWM REVIEW Passed No wastewater plumbing.
12/15/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
12/15/2014 JASON GREEN ENGINEERING REVIEW Approved
12/15/2014 CARL SCHULTZ FIRE REVIEW Approved
12/15/2014 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed