Permit Review Detail
Review Status: Completed
Review Details: PLANS OK TO SUBMIT - COMM
Permit Number - T14CM08506
Review Name: PLANS OK TO SUBMIT - COMM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/11/2014 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 12/11/2014 | RBROWN1 | ADA | REVIEW | Passed | |
| 12/11/2014 | ELEIBOL1 | ENGINEERING | REVIEW | Approved | |
| 12/11/2014 | RONALD BROWN | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/11/2014 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/11/2014 | KEN VAN KARSEN | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
| 12/12/2014 | RSHERRY1 | WWM | REVIEW | Passed | No water meter size change. |
| 12/12/2014 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 12/12/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 12/12/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the water heater installation detail to show the thermal expansion tank. Reference: Section 607.3, IPC 2012. 2. Indirect waste receptors shall not be installed in a closet or cupboard, or unventilated space. Reference: Section 802.3, IPC 2012. |