Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM08491
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/06/2015 | KEN VAN KARSEN | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | T14CM08491 2012 IECC (interior) lighting calculation: provide ComCheck report, or Table C405.5.2(1) building area or (2) space-by-space for budget determination. Ken Van Karsen Electrical Plan Review PDSD, City of Tucson 520-837-4906 Kenneth.VanKarsen@tucsonaz.gov |
12/12/2014 | MARTIN BROWN | FIRE | REVIEW | Approved | |
12/18/2014 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
12/31/2014 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Provide the size of the reduced pressure backflow preventer assembly associated with the water service. Reference: Section 107.2.1, IBC 2012. |
12/31/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide a site drawing showing the size, route, and slope of the building sewer and the location of its connection to the public sewer (verify that there is no septic system serving this address). Reference: Section 107.2.1, IBC 2012. 2. Provide the third-party listing information for the specified lavatory and hair sinks. Reference: Section 303.4, IPC 2012. 3. Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson. 4. Provide tempered water for the lavatory using an approved device conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC. 5. Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, safety pan, and valves. Reference: Sections 503, 504, 606.1, and 607.3, IPC 2012. 6. Construct the temperature & pressure relief piping of materials shown in Table 605.4, IPC 2012 or listed and approved for that use (PVC is not approved). Reference: Section 504.6 (13), IPC 2012. 7. For the use of PEX tubing, provide a branch tube sizing chart showing the correct size of PEX tubing to be used as a substitute for the copper pipe shown on the drawings. Reference: Sections 303.2 and 604.3, IPC 2012. 8. Revise the fixture units used to calculate the total water demand using the values shown in Table E103.3 (2), Appendix E, IPC 2012. Convert the total fixture units to demand (GPM) using Table E103.3 (3), Appendix E, IPC 2012. Reference: Section 604.3, IPC 2012. 9. Verify that the existing pipe size for the water service to the building will not result in water velocities greater than that recommended by the pipe manufacturer (e.g. limit the water velocity to less than 8 FPS for copper, PEX, or PVC piping). Reference: Table 604.3, IPC 2012. 10. If the specified water heater is not supplied with integral heat traps, provide 0.5" of insulation with a maximum conductivity of 0.27 BTU per inch/h F on the first 8 feet of supply and discharge piping. Reference: Section C404.5, IECC 2012. |
12/31/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Demonstrate energy code compliance for the alterations to the building envelope based on the current code. Reference: Sections C101.4.3, C101.5, and C103.2, International Energy Conservation Code 2012. 2. Alterations of an existing building in which the existing ceiling or wall cavities are exposed, shall have the exposed cavities filled with insulation. Reference: Section 101.4.3, IECC 2012. 3. Show that the mechanical systems for the building comply with the current energy code, e.g. provide the COMcheck Mechanical Compliance Certificate. 4. Show that the proposed HVAC system meets the control requirements of Section C403.2.4: set-point overlap restriction, automatic set-back and shut-down controls, automatic start capabilities, and shutoff damper controls. Reference: Section C303.1, International Energy Conservation Code 2012. 5. Specify the required U-factors and Solar Heat Gain Coefficients (SHGC) for the fenestration and doors on the architectural drawings. Reference: Section C103.2, IECC 2012. 6. Provide NFRC fenestration product ratings for the U-factor and the SHGC values on COMcheck or use the appropriate default U-factor and SHGC values from Tables C303.1.3 (1), C303.1.3 (2) and C303.1.3.(3), IECC 2012. Reference: Section C303.1.3, IECC 2012. 7. The minimum insulation for ducts located within unconditioned spaces shall be R-6 with a minimum separation of R-8 between the duct and the exterior of the building. Reference: Section C403.2.7, IECC 2012. 8. Provide the installed weight of the rooftop equipment. Provide structural calculations and details to demonstrate that the installation of the two new rooftop units will not adversely affect the structural integrity of the roof. Reference: Section 302.1, IMC 2012. 9. Provide guards for equipment located within 10 feet of a roof edge or of a walking surface that is elevated more than 30 inches above the adjoining grade. Reference: Section 304.11, IMC 2012. 10. Show the size, routing, and termination of the condensate drain for the roof top A/C unit. Reference: Section 307.2.1, IMC 2012 as amended by the City of Tucson. 11. Provide calculations to show how ventilation will be provided for the occupied spaces. Reference: Section 401.2, IMC 2012. 12. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restroom will be exhausted (i.e. the restroom shall be exhausted whenever air is being supplied to the room). Reference: Section 403.2.1 (4), IMC 2012. 13. Barber shops require a general exhaust air flow rate of 0.5 CFM per square foot. Reference: Table 403.3, IMC 2012. |