Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T14CM08469
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/14/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET S-1; BUILDING DATA: PLEASE CONSIDER REVISING THE OCCUPANCY CLASSIFICATION FROM AN 'A-3' TO A 'U'. NO OCCUPANCY LOAD IS REQUIRED, NO PLUMBING REQUIREMENTS, NO IMPACT FEES, ETC. 2. SHEET S-1; GENERAL NOTES (FOUNDATION); FOOTING NOTE: TWO NOTES INDICATE THE FOOTING CONFIGURATION IS A RECOMMENDATION ONLY AND ANY REQUIRED ADJUSTMENTS TO THE CONFIGURATION SHALL BE DESIGNED BY OTHERS. THAT STATEMENT MUST BE REMOVED FROM THE DRAWING AND THE CALCULATIONS. THE ENGINEER OF RECORD IS RESPONSIBLE FOR THE DESIGN INDICATED IN THE CALCULATIONS AND ON THE DRAWINGS, AND REVISIONS TO THAT DESIGN MUST BE PREPARED BY THE ENGINEER OF RECORD OR APPROVED BY THE ENGINEER OF RECORD PER THE IBC SECTION 107.3.4. 3. SHEET S-1 (ROOF PLAN); STRUCTURAL CALCULATIONS (SHEET 12): THE CUPOLA DOES NOT APPEAR TO BE INCLUDED IN THE CALCULATIONS FOR ITS DESIGN OR EFFECT ON THE LATERAL ANALYSIS OF THE RAMADA. PLEASE VERIFY. 4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/29/2015 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |