Permit Number - T14CM08438
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/10/2014 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 12/10/2014 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 12/10/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A0.0; CODE REVIEW: PER THE IBC SECTION 304, THE OCCUPANCY GROUP SHOULD BE A TYPE B (BUSINESS). REVISE. 2. SHEET A0.0; CODE REVIEW: THE OCCUPANCY LOAD WILL CHANGE FROM 40 TO 1200/100 = 12. REVISE. 3. SHEET A0.0; CODE REVIEW: REVISE THE EXIT WIDTH AND TOILET ROOM REQUIREMENTS FOR THE BUSINESS OCCUPANCY. A SINGLE TOILET WILL STILL BE THE REQUIREMENT. 4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 12/10/2014 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
| 12/11/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Revise the ventilation calculations - use Beuaty salon rather than barber shop and adjust the exhaust volume as needed. |
| 12/11/2014 | KEN VAN KARSEN | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
| 12/11/2014 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 12/11/2014 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 12/11/2014 | RSHERRY1 | WWM | REVIEW | Passed | No water meter change |
| 12/11/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves. Reference: Section 604.9, IPC 2012. |