Permit Number: T14CM08376
Parcel: 11108314B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM08376
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/19/2014 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Completed
12/19/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
12/19/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
12/19/2014 ROBERT SHERRY WATER REVIEW Completed
12/19/2014 RSHERRY1 WWM REVIEW Passed No water meter size change.
12/19/2014 LOREN MAKUS ENGINEERING REVIEW Approved
12/22/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET D1; DEMOLITION KEY NOTES: ALL KEY NOTE REFERENCE NUMBERS SHOULD BE PRECEEDED BY A 'D'. REVISE.
2. SHEET D1; DEMOLITION PLAN: A KEY NOTE 6.4 IS INDICATED AT THE NORTH END OF THIS PLAN. VERIFY (THERE IS NO 6.4 LISTED).
3. SHEET D1; DEMOLITION KEY NOTES: NOTE 10.2 WAS NOT LOCATED ON THE PLAN. VERIFY.
4. SHEET D1; DEMOLITION PLAN; DEMOLITION KEY NOTES: NOTE 15.1 DOES NOT MATCH THE NOTE ON THE PLAN (D16.1). VERIFY.
5. SHEET A1; KEY NOTES: NOTE 8.1 IS INDICATED ON THE PLAN AT THE STAFF ROOM 200.1A, BUT THE KEY NOTES INDICATE 'NOT USED'. VERIFY.
6. SHEET A1; FLOOR PLAN: NOTE 15.2 IS INDICATED ON THE PLAN AT THE DRINKING FOUNTAIN, BUT IS NOT INDICATED IN THE NOTES. VERIFY.
7. GENERAL: VERIFY THAT THE IBC SECTION 407.5.1 IS ADDRESSED IN THIS PROJECT FOR THE AREA OF REFUGE AND ALL REQUIREMENTS OF SECTION 1007 ARE MET.
8. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
12/22/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/23/2014 SPOWELL1 ZONING REVIEW Needs Review
12/23/2014 SPOWELL1 FIRE REVIEW Needs Review