Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2015 MICHAEL ST. PAUL PLANNING-CITY HALL REVIEW Reqs Change P&DS TRANSMITTAL


FROM: Michael St.Paul, Planning Technician

PROJECT:
T14CM08373 (T14SE00019)
2700 East Speedway Boulevard
Cell antennas and new building


TRANSMITTAL: January 8, 2015


COMMENTS: the following comments are relative to an application for a Special Exception relative to cell tower antenna modifications.

A Development Package, per the Administrative Manual 2-06 shall be required for this site. Provide revised parking calculation for the religious use.
01/08/2015 MICHAEL ST. PAUL ZONING REVIEW Reqs Change P&DS TRANSMITTAL


FROM: Michael St.Paul, Planning Technician

PROJECT:
T14CM08373 (T14SE00019)
2700 East Speedway Boulevard
Cell antennas and new building


TRANSMITTAL: January 8, 2015


COMMENTS: the following comments are relative to an application for a Special Exception relative to cell tower antenna modifications.

A Development Package, per the Administrative Manual 2-06 shall be required for this site. Provide revised parking calculation for the religious use.
12/10/2014 MARTIN BROWN FIRE REVIEW Denied Please add 2012 International Fire Code to title sheet as part of applicable building codes and standards.
Batteries contain electrolyte, a hazardous material regulated by the International Fire Code. Please provide calculations indicating total number of batteries (actual and potential), amount of electrolyte per battery, total amount of electrolyte, and how this quantity relates to table 5003.1 of the 2012 IFC.
12/12/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change GENERAL
1. Provide certifications for special inspectors
2. Take the 8 1/2" x 11" AT&T AZTUU1263 Church Bell drawings, blow them up to a 24 x 36 size and include them in the construction document set.
a. Change the Drawing Index to include these new sheets
END OF REVIEW
12/22/2014 CPIERCE1 COMMUNICATIONS REVIEW Completed PER JEFFREY SELIGMAN
12/22/2014 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Reqs Change T14CM08373

1. Provide the panel board mounting height as detail 642/17. The referenced detail 136 is not provided.

2. City of Tucson Outdoor Lighting Code (Ord #10963) compliance: All changes to any outdoor lighting (Circuit #18) must comply with this ordinance. Compare total fixture output to the budget based on property size and location (Table 401.1). The ordinance requires identification of each fixture type (both Full-Cut-Off and un-shielded); and fixture output based on a typical lamp lumen output at the maximum fixture wattage rating.

The 2012 Outdoor Lighting Code may be found on The City of Tucson Website under: www.tucsonaz.gov/pdsd; Codes, Standards, Ordinances & Guidelines; Building Codes.

Ken Van Karsen
Elect Plan Review
PDSD, City of Tucson
520-837-4912
Kenneth.VanKarsen@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
01/09/2015 CPIERCE1 REJECT SHELF RECEIVED