Permit Number: T14CM08369
Parcel: 116205770

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T14CM08369
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/11/2014 MICHAEL ST. PAUL ZONING REVIEW Reqs Change Menlo Park Mercado District's approval stamp is required on all sheets.
12/12/2014 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Date: 12-13-14
Activity: T14CM08369
Address: 225 S. Avenida del Palo Fiero
Applicant: Tom Kirschner

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Residential Code with local amendments. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

PLUMBING PLAN:
1. Provide a trap primer for the floor drain located in the garage, P3201.2.

MECHANICAL PLAN:
2. Gas appliances require combustion air openings, M1701.1. Ensure sufficient air openings are provided for the gas-fired clothes dryer and that any penetrations through the insulation are thermally isolated, N1102.

ELECTRICAL PLAN:
3. Receptacles located below a counter, where the countertop extends more than 6" beyond its support base, shall not be counted as one of the receptacles to serve the small appliance requirements, E3901.4.5. Provide a GFCI protected receptacle to serve the kitchen island, E3901.4.2/3.

OUTDOOR LIGHTING CODE
4. Include the courtyard illumination on the outdoor lighting calculations.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Clayton.Trevillyan@tucsonaz.gov
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/17/2014 AROMERO4 OUT TO CUSTOMER Completed